分享好友 供应首页 频道列表
1/5
芬兰Powernet 电源 后备电源 DC UPS不间断电源  MHE系列图1

芬兰Powernet 电源 后备电源 DC UPS不间断电源 MHE系列

2021-09-23 15:104920询价

价格:¥0.00/件

品牌:Powernet

发货:3天内

发送询价

芬兰Powernet 电源 后备电源 DC UPS不间断电源  MHE系列

12/24/48VDC  体积小巧  易于安装  结构安全  EMC EN55022B

 温度补偿  深度放电保护  掉电信号

 带插头或螺钉端子电源连接  15A 输出 MCB  可选防拆开关

Technical Specifications

AC Input

MHE 24-1500

MHE 48-2000

MHE 60-2000

MHE 110-2000

MHE 125-2000

MHE 220-2000

Input voltage

Nominal 100VAC - 250VAC, rated full power range 180VAC – 275VAC

 

Input range

Full range 85 – 300 VAC:

Reduced output power 85-180VAC, linear derating, 920W @ 85 VAC , see curve page 3

Temporary high voltage range 275-300VAC, continuous supply voltage above 275VAC not recommended

Start-up / shut down limits

Start-up voltage 90VAC / Shut down at 85 VAC

Shut down over voltage limit 300VAC / re-start at 290VAC

Reduced output power

85 – 180 VAC, Linear derating, 920W @ 85 VAC

Input frequency

Rated 45 - 66 Hz, reduced power at 35 - 45 Hz. Shut down at 35 Hz

Maximum current

9 A

12 A

12 A

12 A

12 A

12 A

Inrush current

Active limitation <20A, ETS 300 132-1

Power factor (typical)

>0.99 at 85-275VAC input

THD (typical)

< 5% @ 100%, < 9% @ 50% at 85-275VAC input

Input protection

External MCB 16A C-curve, Internal varistor and gas discharge tube for transient surge protection,

Automatic shut-off above 300 VAC (restart at 290 VAC)

Generator start-up ramp

7 seconds ramp from 200W to full 2kW controlled by Input power, used with generator input supply

(User programmable feature, enable/disable, default disable)

Start-up delay feature

User Programmable start-up delay 0-120sec, default 0sec

 

DC Output

MHE 24-1500

MHE 48-2000

MHE 60-2000

MHE 110-2000

MHE 125-2000

MHE 220-2000

Voltage range

21-33 VDC

42-59 VDC

51-72 VDC

90-150 VDC

100-160 VDC

178-280 VDC

Voltage factory setting

27.24 VDC

54.48 VDC

68.10 VDC

122.58 VDC

136.20 VDC

245.16 VDC

Maximum current

@ nominal output

62.5 A

@ 24 V

41.7 A

@ 48 V

33.3 A

@ 60 V

18.5 A

@ 108 V

16.7 A

@ 120 V

9.3 A

@ 216 V

Constant output power

1500 W

2000 W

Short circuit current

< 65 A

< 45 A

< 35 A

< 20 A

< 20 A

< 10 A

Type of Current limit

MHE rectifier supplies constant short circuit current 500sec, then hiccup mode in 500sec cycles

Hold-up time

> 20 ms at 80% load, output voltage reduces from float voltage to nominal

Static voltage regulation

± 0.5 % (load, line, temperature)

Dynamic load regulation

± 5.0 % for 10%-90% or 90%-10% load step, recovery time < 2.0 ms

Ripple and noise

< 50 mVp-p

< 100 mVp-p

< 115 mVp-p

< 225 mVp-p

< 250 mVp-p

< 450 mVp-p

 

Output protection

Overvoltage shutdown

Power limiting from temperature, under frequency, over voltage and under voltage

Internal over temperature protection

 

Features

MHE 24-1500

MHE 48-2000

MHE 60-2000

MHE 110-2000

MHE 125-2000

MHE 220-2000

Efficiency, typical

35-80% load, Vin 230VAC

> 95 %

> 96 %

> 96 %

> 96 %

> 96%

> 95%

MTBF, calculated

> 1 800 000 h @ 25oC, Telcordia SR-332, Method I-D, Ground Fixed uncontrolled environment

Dielectric strength, type test

Input – GND (basic), 2 kVAC or 2.83 kVDC, 1 min Input - Output (reinforced) 3.75kVac or 5.3 kVDC, 1 min

Output – GND (basic) 2 kVAC or 2.83 kVDC, 1 min

Load current share

± 5 % from true average current between the modules (>50% load, controlled by VIDI)

Alarms

Mains fault alarm, Low output voltage alarm, Overvoltage shutdown alarm, Rectifier alarm,

Temperature Alarm, Totally +40 configurable system alarms via VIDI controller

Visual Indications

LED: Green/Red/Yellow, see the rectifier user manual for more details

Energy saving mode

See Efore VIDI controller manual


反对 0
举报 0
收藏 0
评论 0
联系方式